7.1.2 Deflection-type d.c. bridge
A deflection-type bridge with d.c.
excitation is shown in Figure 7.2. This differs from the Wheatstone bridge
mainly in that the variable resistance Rv is replaced by a fixed
resistance R1 of the same value as the nominal value of the unknown
resistance Ru. As the resistance Ru changes, so the
output voltage V0 varies, and this relationship between V0
and Ru must be calculated.
This relationship is simplified if we
again assume that a high impedance voltage measuring instrument is used and the
current drawn by it, Im, can be approximated to zero. (The case when
this assumption does not hold is covered later in this section.) The analysis
is then exactly the same as for the preceding example of the Wheatstone bridge,
except that Rv is replaced by R1. Thus, from equation (7.1), we
have:
V0 = Vi(Ru/(Ru
+ R3) - R1/(R1 + R2) (7.3)
When Ru is at its nominal
value, i.e. for Ru = R1, it is clear that V0 =
0 (since R2 = R3). For other values of Ru, V0
has negative and positive values that vary in a non-linear way with Ru.
Example 7.1
A certain type of pressure
transducer, designed to measure pressures in the range 0–10 bar, consists of a
diaphragm with a strain gauge cemented to it to detect diaphragm
deflections. The strain gauge has a
nominal resistance of 120 Ω and forms one arm of a Wheatstone bridge circuit,
with the other three arms each having a resistance of 120 Ω. The bridge output
is measured by an instrument whose input impedance can be assumed infinite. If,
in order to limit heating effects, the maximum permissible gauge current is 30
mA, calculate the maximum permissible bridge excitation voltage. If the
sensitivity of the strain gauge is 338 mΩ /bar and the maximum bridge
excitation voltage is used, calculate the bridge output voltage when measuring
a pressure of 10 bar.
Solution
This is the type of bridge circuit
shown in Figure 7.2 in which the components have the following values:
R1 = R2
= R3 = 120 Ω
Defining I1 to be the
current flowing in path ADC of the bridge, we can write:
Vi = I1/(Ru
+ R3)
At balance, Ru = 120 and
the maximum value allowable for I1 is 0.03 A.
Hence:
Vi = 0.03(120
+ 120) = 7.2 V
Thus, the maximum bridge excitation
voltage allowable is 7.2 volts.
For a pressure of 10 bar applied, the
resistance change is 3.38 Ω, i.e. Ru is then equal to 123.38 Ω.
Applying equation (7.3), we can
write:
V0 = Vi{Ru/(Ru
+ R3) - R1/(R1 + R2)} = 7.2 {123.38/243.38 –
120/240} = 50 mV
Thus, if the maximum permissible
bridge excitation voltage is used, the output voltage is 50 mV when a pressure
of 10 bar is measured.
The non-linear relationship between
output reading and measured quantity exhibited by equation (7.3) is
inconvenient and does not conform with the normal requirement for a linear
input–output relationship. The method of coping with this non-linearity varies
according to the form of primary transducer involved in the measurement system.
One special case is where the change
in the unknown resistance Ru is typically small compared with the
nominal value of Ru. If we calculate the new voltage V’0
when the resistance Ru in equation (7.3) changes by an amount
V’0 = Vi{(Ru
+
The change of voltage output is
therefore given by:
If
This expression describes the
measurement sensitivity of the bridge. Such an approximation to make the
relationship linear is valid for transducers such as strain gauges where the
typical changes of resistance with strain are very small compared with the
nominal gauge resistance.
However, many instruments that are
inherently linear themselves at least over a limited measurement range, such as
resistance thermometers, exhibit large changes in output as the input quantity
changes, and the approximation of equation (7.5) cannot be applied. In such
cases, specific action must be taken to improve linearity in the relationship
between the bridge output voltage and the measured quantity. One common
solution to this problem is to make the values of the resistances R2
and R3 at least ten times those of R1 and Ru
(nominal). The effect of this is best observed by looking at a numerical
example.
Consider a platinum resistance
thermometer with a range of 0° –50°C, whose resistance at 0°C is 500 Ω and
whose resistance varies with temperature at the rate of 4 Ω/°C. Over this range
of measurement, the output characteristic of the thermometer itself is nearly
perfectly linear. (N.B. The subject of resistance thermometers is discussed
further in Chapter 14.)
Taking first the case where R1
= R2 = R3 = 500 Ω and Vi = 10 V, and applying
equation (7.3):
At 0°C; V0 = 0
At 25°C; Ru = 600 Ω and V0 =
10(600/1100 – 500/1000) = 0.455 V
At 50°C; Ru = 700 Ω and V0 = 10(700/1200
– 500/1000) = 0.833 V
This relationship between V0
and Ru is plotted as curve (a) in Figure 7.3 and the non-linearity
is apparent. Inspection of the manner in which the output voltage V0
above changes for equal steps of temperature change also clearly demonstrates
the non-linearity.
For the temperature change
from 0 to 25°C, the change in V0 is
(0.455 – 0) =
0.455 V
For the temperature change
from 25 to 50°C, the change in V0 is
(0.833 -
0.455) = 0.378 V
If the relationship was linear, the
change in V0 for the 25–50°C temperature step would also be 0.455 V,
giving a value for V0 of 0.910 V at 50°C.
Now take the case where R1
= 500 Ω but R2 = R3 D 5000 Ω and let Vi = 26.1
V:
At 0°C; V0 = 0
At 25°C; Ru = 600 Ω
and V0 = 26.1(600/5600 – 500/5500) = 0.424 V
At 50°C; Ru = 700 Ω
and V0 = 26.1(700/5700 – 500/5500) = 0.833 V
This relationship is shown as curve
(b) in Figure 7.3 and a considerable improvement in linearity is achieved. This
is more apparent if the differences in values for V0 over the two
temperature steps are inspected.
From 0 to 25°C, the change in V0 is 0.424 V
From 25 to 50°C,
the change in V0 is 0.409 V
The changes in V0 over the
two temperature steps are much closer to being equal than before, demonstrating
the improvement in linearity. However, in increasing the values of R2
and R3, it was also necessary to increase the excitation voltage from
10 V to 26.1 V to obtain the same output levels. In practical applications, Vi
would normally be set at the maximum level consistent with the limitation of
the effect of circuit heating in order to maximize the measurement sensitivity
(V0/
The importance of this inherent
non-linearity in the bridge output relationship is greatly diminished if the
primary transducer and bridge circuit are incorporated as elements within an
intelligent instrument. In that case, digital computation is applied
to produce an output in terms of the
measured quantity that automatically compensates for the non-linearity in the
bridge circuit.
Case where current drawn by measuring
instrument is not negligible
For various reasons, it is not always
possible to meet the condition that the impedance of the instrument measuring
the bridge output voltage is sufficiently large for the current drawn by it to
be negligible. Wherever the measurement current is not negligible, an
alternative relationship between the bridge input and output must be derived
that takes the current drawn by the measuring instrument into account.
Thevenin’s theorem is again a useful
tool for this purpose. Replacing the voltage ´ source Vi in Figure
7.4(a) by a zero internal resistance produces the circuit shown in Figure
7.4(b), or the equivalent representation shown in Figure 7.4(c). It is apparent
from Figure 7.4(c) that the equivalent circuit resistance consists of a pair of
parallel resistors Ru and R3 in series with the parallel
resistor pair R1 and R2. Thus, RDB is
given by:
RDB = - R1R2/(R1
+ R2) + RuR3/(Ru + R3) (7.6)
The equivalent circuit derived via
Thevenin’s theorem with the resistance ´ Rm of the measuring
instrument connected across the output is shown in Figure 7.4(d). The open-circuit
voltage across DB, E0, is the output voltage calculated earlier
(equation 7.3) for the case of Rm = 0:
E0 = V(Ru/(Ru
+ R3) - R1/(R1 + R2) (7.7)
If the current flowing is Im
when the measuring instrument of resistance Rm is connected across
DB, then, by Ohm’s law, Im is given by:
Im = E0/(RDB
+ Rm) (7.8)
If Vm is the voltage
measured across Rm, then, again by Ohm’s law:
Vm = ImRm =
E0Rm/(RDB + Rm) (7.9)
Substituting for E0 and RDB
in equation (7.9), using the relationships developed in equations (7.6) and
(7.7), we obtain:
Vm = Vi [Ru/(Ru
+ R3) - R1/(R1 + R2)] Rm /R1R2/(R1
+ R2) + RuR3/(Ru + R3) +
Rm
Simplifying:
Vm = ViRm(RuR2
- R1R3) / R1R2(Ru + R3) +
RuR3(R1 + R2) + Rm(R1
+ R2)(Ru + R3) (7.10)
Example 7.2
A bridge circuit, as shown in Figure
7.5, is used to measure the value of the unknown resistance Ru of a strain
gauge of nominal value 500 Ω. The output voltage measured across points DB in
the bridge is measured by a voltmeter. Calculate the measurement sensitivity in
volts/ohm change in Ru if
(a) the resistance Rm of
the measuring instrument is neglected, and
(b) account is taken of the value of
Rm
Solution
For Ru = 500 Ω, Vm = 0.
To determine sensitivity, calculate Vm for Ru = 501 Ω.
(a) Applying equation (7.3): Vm = Vi
[Ru/(Ru + R3) - R1/(R1 +
R2)]
Substituting in values: Vm = 10 (501/1001 – 500/1000) = 5.00 mV
Thus, if the resistance of the
measuring circuit is neglected, the measurement sensitivity is 5.00 mV per ohm
change in Ru.
(b) Applying equation (7.10) and
substituting in values:
Vm = 10 × 104 ×
500(501 – 500) / 5002 (1001) + 500 × 501(1000) + 104 ×
1000 × 1001 = 4.76 mV
Thus, if proper account is taken of
the 10 kΩ value of the resistance of Rm, the true measurement
sensitivity is shown to be 4.76 mV per ohm change in Ru.
No comments:
Post a Comment
Tell your requirements and How this blog helped you.